Products
Home > Products > Switchgear & Transformer
SC6-24 SF6 Load Break Switch
Standard Specification

++++General:

      SC6-24 SF6 load break switch, an switchgear with the rated voltage of 12KV/24/KV/36/KV, adopted with SF6 gas as an arc-extinguishing ad insulation medium, including the three contactors for switching-on and switching-off and to ground, and is characteistic in its small volume, its convenient installation and operation and its the great adaptability with surroundings.

       SC6-24 SF6 load break switch and RLS-24D of SF6 load switch plus fuse combination canfunctionto protect and controlthe electric equipmentsfor power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation. 
      SC6-24 SF6 load break switch and RLS-24D load switch plus fuse combination are complied withthe standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc.. 
++++Service environment:
     a) Airtemperature 
        Maximumtemperature: +40¡æ; Minimumtemperature:-5¡æ
     b) Humidity 
         Monthly average humidity 95%; Daily average humidity 90%. 
     c) Altitude above sea level 
         Maximum installation altitude: 2500m 
     d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 
     e) Nofrequent violent shake
++++Main technical specifications:


 No

 
  Item

   Unit 

 Parameter

 1

 Rated voltage

  kV

 24

 2

 Rated frequency

      Hz 

   50/60

 3 

 Rated current 

 A 

 630/800

 4 

                                                           wet 

1min Power frequency  withstand voltage
                                                          dry 

 kV 

50

 

60

 5

 Lightning impulse withstand voltage

     kV 

   125/150

 6 

 Rated short circuit breaking current (peak)

   kA

  63

 7

   Rated activeload and close circuit breaking current

   A 

  50

 8

   Rated transferring current 

 A 

   1200

 9

   Rated short circuit making current (peak)

 kA

  63

 10

  Rated cable(line) charging breaking current 

  A

  50 and 10

 11 

   Cable charge breaking current in earthing fault 

 A 

  20

 12

 Rated withstand current (peak)

 kA

  63

  13 

 Short time withstand current (2s)

 kA

 25

 14

            Mechanism life 

 times 

  2000

Note: For short circuit breaking and peak current isbased on Fuseplus combination.
top
Product Catalog
Products